40°C Heat Pump – Low Temp Heat Pump – Co-Therm

Modelo comercial

Co-Therm LTHP

Familia

Co-Therm

Type

Bomba de calor industrial con recuperación de calor

Capacidad agua caliente

1,177,467 BTU/h / 98 TR

Capacidad agua fría

912,000 BTU/h / 76 TR

Temperatura Agua Caliente

40 °C

Chilled Water Temperature

7 °C

Compressor

Scroll

Refrigerante

R-410

Voltage

460V/F/60Hz

Recuperación de calor

Sí

Producción simultánea

Agua helada + agua caliente

Disponibilidad

Fabricación bajo pedido

Applications

Aplicaciones de baja temperatura, Hoteles y resorts, Hospitales, Spas y centros deportivos, Industria, Alimentos y bebidas, Procesos con demanda simultánea de agua helada y agua caliente

Ficha técnica

https://tecsir.com/ficha-tecnica/FTEC-LT-HP.pdf

Modalidad comercial

Cotización

Co-Therm Low Temp Heat Pump: Low-temperature heat pump manufactured by Grupo TECSIR in Mexico with the highest quality standards. Designed to simultaneously produce hot water and cold water in a single system, optimizing space and energy consumption. The Co-Therm generates hot water at 40 °C and cold water at 7 °C, with a capacity of 1,177,467 BTU/h for hot water and 76 TR for cold water, offering a comprehensive solution for applications that require both temperatures continuously.

Features

  • Compresores Scroll
  • Refrigerant R-410A
  • Shell-and-tube evaporator (Cu)
  • Shell-and-tube condenser (Ti)
  • Hot water 40 °C / cold water 7 °C
  • Flanged CPVC and carbon steel 150# connections
  • Star–delta starter (ΥΔ)
  • Voltage 460V/3Ph/60Hz

Specialized equipment for industrial, commercial, and recreational applications that require simultaneous water cooling and heating. Ideal for projects seeking to reduce the use of separate equipment, take advantage of heat recovery, and maintain a constant supply for both comfort and process needs.

Applications and industries:

  • Pool heating in hotels, resorts, clubs, and gyms
  • Hotels and spas (hot water for showers, hydromassage, and pool heating)
  • Hospitals and clinics (domestic hot water and area cooling)
  • Sports and recreational centers (heated pools and air conditioning)
  • Industrial processes requiring simultaneous cooling and hot water (cleaning, rinsing, preheating)
  • Aquatic centers (optimal water temperature maintenance and area conditioning)
  • Wellness and aquatic therapy facilities (therapeutic pools, hydrotherapy)
  • Mixed-use buildings (hot water supply and centralized HVAC)